Configured for switching AC or DC loads in industrial automation systems, the Allen-Bradley 1769-OW8I (1769-OW8I Discrete Output Module) provides direct physical/electrical execution.
| Parameter | Specification |
| Model | 1769-OW8I |
| Brand | Allen-Bradley |
| Origin | United States |
| Weight | 0.50 lbs (0.23 kg) |
| Dimensions | Standard Compact I/O module form factor |
| Operating Temp | 0 deg C to +60 deg C |
| Power Consumption | 125 mA @ 5.1 VDC bus current, 100 mA @ 24 VDC bus current |
| Output Type | Relay (mechanical contact, normally open) |
| Number of Outputs | 8 individually isolated points |
| Operating Voltage Range | 5 to 265 VAC / 5 to 125 VDC |
| Signal Delay Time | 10 ms (ON state response) |
| Heat Dissipation | 2.83 W |
| Mounting Style | DIN rail or panel mount |
| Compatible Controllers | MicroLogix 1500, CompactLogix controllers |
The Allen-Bradley 1769-OW8I coordinates physical relay transitions via internal bus register structures interfacing with external architectures over Profinet / EtherNet/IP deterministic networks. The mechanical contact mechanisms provide isolation from backplane logic electronics. The power supply distance rating of 8 modules limits bus load drops, ensuring reliable I/O density scaling inside CompactLogix assemblies. By dampening switching transients through onboard optical isolation, the component prevents electrical noise from interrupting system data packets.
Q: Does the 1769-OW8I module support the hot-swap feature (Removal and Insertion Under Power) during operation?
A: No. Compact I/O modules do not support RIUP. The system power supply must be completely deactivated before removing or inserting this module to prevent backplane bus corruption or structural damage to the interconnect pins.
Q: What are the insulation constraints regarding the individual channel-to-channel isolation?
A: Each relay output is individually isolated with an insulation rating of 265 VAC basic insulation, and 150 VAC IEC Class 2 reinforced insulation. This architecture allows different voltage phases and potentials to be wired to adjacent terminals safely.
Q: What are the wire gauge specifications for the screw terminals to ensure secure load connections?
A: The terminal block accommodates solid copper wire sized from 22 to 14 AWG, or stranded copper wire rated for 90 deg C sized from 22 to 16 AWG.